These are the basic requirements that a panelboard rated 1000 volts or less must meet in order to be used as service equipment:
A. Service disconnecting means must be provided.
B. Each service disconnect provided must have a switching feature that disconnects all conductors from the service-entrance conductors and that is suitable for use as a service disconnect. There is one exception: the neutral service conductor can be disconnected by removing the wires from the pressure wire connectors on the service neutral bus as noted in Section 230.75 of the NEC.
Disconnects and overcurrent protection which are located on the supply side of the service disconnecting means may be located behind a deadfront or screwed-on cover if:
- The circuit being controlled is installed as part of the Certified (Listed) panelboard.
- The circuit being controlled in contained within the panelboard enclosure.
- The panelboard is marked, adjacent to the main disconnect(s) to alert the user that the main(s) does not disconnect control and instrument circuits.
In general, snap, toggle or similar switches, are not acceptable because their internal electrical spacings are too small.
Circuit breakers, either molded case, fused or in combination with ground-fault circuit interrupters, are suitable for use as service disconnects. Other devices that are used to protect individual circuits, circuits within equipment or appliances, or circuit protectors without on and off features are not suitable for use as service disconnects.
The removal of a plug or cartridge fuse from its fuseholder, while serving to de-energize the circuit, does not provide service disconnection. Panelboard switches, pullout switches and some industrial control switches are suitable as service disconnects. Note that pullout switches, while they serve as a fuse puller, do have switchblades and contact jaws and are tested as switches.
C. Overcurrent protection suitable as branch or feeder protection must be provided for service conductors. Miscellaneous, miniature and micro fuses, thermal cutouts, relays and other supplementary overcurrent protection are not acceptable; however, “special purpose fuses” that are suitably rated for use as branch circuit, feeder, or service overcurrent protection may be used if:
- The fuses are non-interchangeable with fuses of incompatible ratings, and
- The panelboard is marked for use with the specific special purpose fuses.
D. The number of service disconnects and overcurrent devices must conform to the NEC, Section 230.71.
E. As required in Section 230.95 of the NEC, panelboards rated for use on solidly grounded wye electrical services of more than 150 volts to ground must provide ground-fault protection for each service disconnect rated 1000 amperes, or more. An exception is covered under Item 53.
F. There must be provision for connecting a grounded service conductor and a grounding-electrode conductor. If there is a neutral bus, a means to bond the panelboard enclosure or mounting pan to the neutral bus is required unless the bus is mounted in electrical contact with the enclosure or pan.
In general, the grounding-electrode connection in service equipment is required to be made to the grounded service conductor at the neutral bar. However, Section 250.24(A)(4) of the NEC permits this connection to be made to the equipment grounding terminal bar, provided the main bonding jumper is a wire or a busbar and is installed from the neutral bar to the equipment grounding terminal bar. If in a panelboard suitable for use as service equipment, the main bonding jumper wire or busbar is provided for field installation, instructions are marked on the panelboard for proper installation of the jumper.
A panelboard with the neutral insulated from the enclosure may be marked “Suitable for use as service equipment when not more than six main disconnecting means are provided” when the following conditions are met:
A. There must be at least one combination of switching units that can be mounted to occupy all available space for switching units; and, whether by using handle ties or similar devices, not more than six main disconnects will result (including factory-installed disconnects).
B. With this combination of switching units, no more than six overcurrent-protective devices will be connected to each ungrounded service conductor.
Note that a panelboard marked “Suitable for use as service equipment when not more than six main disconnecting means are provided” may permit some combinations of switching units varying in ampere ratings and physical size that would exceed the six disconnect rule on a completely filled panelboard. The six disconnect rule can be exceeded if handle ties are not installed where needed.
Panelboards marked as noted above and used as service equipment must have the neutral bonded to the enclosure as required by Section 408.3(C) of the NEC. These panelboards are provided with means to accomplish this bonding. When the panelboard is not used as service equipment, the neutral bonding means must not be installed. This would violate Section 250.24(A)(5) of the NEC and would constitute a fire hazard as noted in Item 50 of this marking guide.
A panelboard with the neutral factory-bonded to the enclosure is marked “Suitable only for use as service equipment. Install no more than six main disconnecting means.”
Some panelboards may have the required number of handles and service overcurrent devices, when the maximum number of the smallest units are installed and used without handles ties or similar devices. These panelboards may have the shorter marking “Suitable for use as service equipment” or “Suitable only for use as service equipment.”
A panelboard intended for service equipment use must have the marking “Service Disconnects” near the switch or circuit breaker handles. If this is not done in the factory, pressure-sensitive labels must be provided. This marking identifies the service disconnects when branch disconnects are also present. This is required by Section 230.70(B) of the NEC.