Dampers Marking and Application Guide

A guide to duct fire dampers and the differences in damper CFM design for safety and adherence to standards in HVAC systems. Explains certification markings, intended uses, limitations, and evaluation standards.

Fire dampers

Fire dampers are designed to close automatically when heat is detected and are used to restrict the spread of fire where ducts and air transfer openings penetrate fire walls, fire barriers, fire partitions, horizontal assemblies and shaft enclosures. The building codes specify where fire dampers are required and establish how the fire damper is to be installed in the field.

Fire dampers are available in two types: static fire dampers and dynamic fire dampers. Fire dampers for use in either static systems or dynamic systems are certified by UL Solutions with an hourly fire-protection rating, either 1-1/2 or 3 hours.

fire damper

Fire dampers for use in static systems, as their name implies, are only to be used in duct systems or penetrations where the HVAC system is automatically shut down in the event of a fire.

Fire dampers for use in dynamic systems are required at locations where fan pressure and airflow continue to operate during a fire incident, and as such, the dampers are expected to operate (close) against the air velocity and pressure produced by the system fan. In addition to an hourly fire-protection rating, fire dampers for use in dynamic systems are also provided with an airflow rating which indicates the maximum velocity (damper open) and static pressure (damper closed) for which the damper is designed. Refer to Airflow Ratings for a more detailed explanation of the limitations of the ratings.

damper through wall

Smoke dampers

smoke damper

Smoke dampers are used to restrict the movement of smoke where ducts and air transfer openings penetrate assemblies that are designed to restrict the movement of smoke. These devices are installed to operate automatically, controlled by a smoke detection system, and, where required, capable of being positioned from a remote command station.

Smoke dampers may be required where ducts penetrate through smoke barriers or smoke partitions, or at other locations within an engineered smoke control system. Smoke dampers can be used in HVAC systems where the fans are shut down in the event of fire and can also be used in smoke control systems designed to operate during a fire incident. Smoke dampers are designed to operate against air velocity and fan pressure.

Smoke dampers listed by UL Solutions have a leakage class rating that indicates the level of air leakage measured through the damper under test conditions. Leakage ratings are identified as Class Designation I, II or III as shown in the following table. Leakage ratings of smoke dampers are established at a minimum differential pressure of 4 in. water gauge (WG), across the closed damper. Leakage rates may also be established at higher differential pressures, in increments of 2 in. water gauge. The model codes require a Class I or II rated smoke damper.

Maximum Leakage (cfm/ft2)

Class 4 In. WG 6 In. WG 8 In. WG 10 In. WG 12 In. WG
III 80.0 96.0 112.0 125.0 140.0
II 20.0 24.0 28.0 31.5 35.0
I 8.0 9.5 11.0 12.5 14.0

Duct outlet protection system A (As Permitted by the Individual Designs within BXUV)

system a longitudinal cross section
system b longitudinal cross section

Duct outlet protection system B (Permitted where a steel duct with a hinged-door damper is described in a fire resistance-rated design)

system b longitudinal cross section
system b transverse cross section
Category Code Category Name Standard Used
BZGU Air Terminal Units UL 263
BZZU Ceiling Air Diffusers UL 263 and UL 555C
CABS Ceiling Dampers UL 263 and UL 555C
EMME Dampers for Fire Barrier and Smoke Applications UL 555, UL 555S

Installation instructions

damper side illustration

Each damper shipment is supplied with a copy of the installation instructions appropriate for the specific damper model. These instructions are an integral part of the UL Solutions certification on the dampers as UL Solutions reviews the instructions as part of the damper listing process. The instructions contain the information necessary to properly install the damper as well as limitations on the installation of the product such as the type of floor or wall construction that is required for the correct installation.

Airflow ratings

Dynamic fire dampers, smoke dampers and combination fire-smoke dampers are marked with airflow and closure pressure ratings. These ratings represent the maximum airflow and closure pressure ratings tested for that product. The closure pressure rating is not the pressure drop across an open damper.

airflow sticker

Fire damper illustration

fire damper illustration

Smoke and combination fire-smoke damper illustration

smoke and combination fire-smoke damper illustration

Ceiling damper illustration

ceiling damper illustration

Corridor damper illustration

corridor damper illustration

UL Certified Mark

Here are some examples of the UL Marks you may encounter:

UL certified mark
UL certified mark

UL Listing Mark

Figure 3 - UL Listed Mark

UL Classification Mark

UL classified mark