Accessible, front – An enclosure in which incoming and outgoing field termination points are accessible from the front. Other connections shall be permitted to be rear or side accessible. If necessary, a limited number of devices shall be permitted to be removed to achieve this accessibility.
Accessible, rear – An enclosure in which all incoming and outgoing field termination points are accessible from the rear. Other connections shall be permitted to be front or side accessible. If necessary, a limited number of barriers or covers shall be permitted to be removed to achieve this accessibility.
Ampacity – The current in amperes a conductor can carry continuously under the conditions of use without exceeding its temperature rating.
Barrier – A partition for the insulation or isolation of electric circuits or electric arcs.
Bonding – The permanent joining of metallic parts to form an electrically conductive low impedance path that will assure electrical continuity and the capacity to conduct safely any current likely to be imposed.
Bus – A conductor, or group of conductors, that serves as a common connection for two or more circuits.
Bus, branch – A bus that originates at a section bus and terminates in one or more overcurrent devices.
Bus, ground – A bus to which the equipment grounding conductors from individual pieces of equipment are connected and which, in turn, is connected to the grounding electrode conductor at one point. It provides a continuous ground in multiple equipment sections through which it passes. See Figure 2.1.
Bus, neutral – A bus having the appropriate number of terminals to provide for the connection of the neutral line and load conductors. See Figure 2.1.
Bus, section – That portion of the bus structure that serves one or more overcurrent devices in the switchboard section and comprises that part of the bus between the supply bus and branch bus. See Figure 2.1.
Bus, splice – A bus that electrically connects switchboard sections. See Figure 2.1.
Bus, supply – A bus that is intended primarily for conducting electric power from the source to the main section of a switchboard. See Figure 2.1.
Bus, through – A bus that extends through a switchboard section. It is sometimes called a horizontal, cross or main bus. See Figure 2.1.
Circuit breaker – A device designed to open and close a circuit by non-automatic means, and to open the circuit automatically on a predetermined overcurrent, without injury to itself when properly applied within its rating.
Circuit breaker, molded case – A circuit breaker which is assembled as an integral unit in a supporting and enclosing housing of insulating material.
Continuous current – The amount of current a conductor, a device or a piece of equipment can carry continuously for an indefinite period of time without exceeding its allowable temperature rise.
Current rating – The designated maximum direct or alternating current in rms amperes at rated frequency that a device can carry continuously under specified conditions.
Dead-front switchboard – A switchboard which has no exposed live parts on the front.
Device – A component of an electrical system that is intended to carry or control, but not utilize, electrical energy.
Disconnecting means – A device, or a group of devices, or other means by which the conductors of a circuit can be disconnected from their source of supply.
Double-ended switchboard (multiple source) – A switchboard construction that provides for the connection of two supply sources, such as a utility service and an on-site generator. See Figures 2.2 and 2.3 for typical examples.
Fuse – A protective device which opens by the melting of a current-sensitive element during specified overcurrent conditions.
Fusible switch – A switch in which one or more poles have a fuse in series in a composite unit.
I2t (ampere squared seconds) – An expression related to the circuit energy as a result of current flow. The “I2” stands for the square of the effective (rms) let-through current and the “t” stands for the time of current flow in seconds. “I2t” is a common expression for the circuit energy between the initiation of the fault current and the clearing of the circuit.
Inlet – A permanently mounted plug intended to receive power from a cable connector.
Interlock – An electrical or mechanical component actuated by the operation of a device or other means, with which it is directly associated to govern succeeding operations of the same or allied devices.
Interrupting rating – The highest current at rated voltage that a device is intended to interrupt under standard test conditions.
Main device – A single device that disconnects all ungrounded conductors, other than control power conductors when used, from the supply bus. See Figure 2.1.
Main section(s) – A portion of a switchboard where the main or service disconnect device(s) is located. The section shall also be permitted to contain utility meters or other instruments. Incoming line conductors may be terminated in this section. See figure 2.1.
Neutral – Neutral refers to a conductor (when one exists) of a polyphase circuit or single-phase, 3-wire circuit which is intended to have a voltage such that the voltage differences between it and each of the other conductors are approximately equal in magnitude and are equally spaced in phase, such as the:
- Center point of a wire connected system
- Midpoint of a 3-wire, single phase system
- Midpoint of one side of a delta connected system
Outlet – A device that is intended to provide power to an inserted plug, and that is installed as a fixed receptacle on equipment.
Rating – A designated limit of operating characteristics based on definite conditions.
Rating plug – A self-contained portion of a circuit breaker that is interchangeable and replaceable in a circuit breaker trip unit by the user. It sets the Rated Current (In) of the circuit breaker.
Service equipment – The necessary equipment, usually consisting of a circuit breaker or switch and fuses, and their accessories, located near the point of entrance of supply conductors to a building or other structure, or an otherwise defined area, and intended to constitute the main control and means of cutoff of the supply.
Short-circuit current rating – The maximum RMS available current to which a device can be connected. The rating is expressed in amperes and volts.
Switch – A device, manually operated, unless otherwise designated, for opening and closing or for changing the connection of a circuit.
Switchboard – A large single panel, structural frame or assembly of panels or structural frames on which may be mounted, on the face or back or both: switches, overcurrent, and other protective devices, buses, and instruments.
Note: Switchboards may be accessible from the rear as well as from the front and are not intended to be installed in cabinets.
Switchboard enclosure – An enclosure that encloses one or more switchboard sections or switchboard interiors, or provides auxiliary wiring space for an adjacent switchboard section.
Switchboard interior – The interior part of a switchboard intended to be installed in a switchboard enclosure to become the equivalent of a switchboard section.
Switchboard section – That portion of a switchboard that is prevented by the structural framework from being physically separated into smaller units.
Note: Framework that is welded or joined with steel rivets over 1/4 inch (6.4 mm) in diameter is considered to constitute a single section. However, framework that is joined with one-way (tamper-proof) bolts is not considered to constitute a single section. An assembly consisting of an enclosure and terminal blocks or bus bars is considered to be a switchboard section.
Symmetrical current – Alternating current having no offset or transient component and, therefore, having a wave form essentially symmetrical about the zero axis. Symmetrical current is expressed in terms of rms A.
Tap – A terminal or provision for a terminal intended for field wiring that is located on the supply side of the service disconnecting means, for uses permitted by the installation rules of the country of installation.