27. Non-Conducting Enclosure – A circuit breaker not intended for use in a metal enclosure is marked “Suitable for use in a non-conducting enclosure only.”
28. Ventilated Enclosure – A circuit breaker for use in a ventilated enclosure is marked to identify the enclosure or to indicate the proper enclosure size, and location and size of the ventilating openings.
29. 40°C – A thermal-magnetic circuit breaker that is suitable for use in ambients up to 40°C is marked “40°C.” Circuit breakers with electronic type trip units are not affected by the ambient temperature and are not required to be marked to indicate the suitability. These devices may be used in a 40°C ambient unless marked 25°C.
30. Current Limiting – A circuit breaker that meets UL requirements for current limiting is marked “Current Limiting.” The breaker is also marked with the peak current (Ip) and I²t let-through and related frequency, or to reference a publication available from the manufacturer with this same information. These let-through current curves indicate the let-through currents versus prospective fault current across the range from the threshold level, where the breaker starts to exhibit current limiting characteristics, to the maximum interrupting rating, with at least one intermediate point also indicated. UL’s definition of a current limiting breaker is one that does not use a fusible element and, when operating within its current limiting range, limits the let-through I²t to less than the I²t of a 1/2-cycle wave of the available symmetrical current.
31. Class CTL – Circuit breakers for Class CTL panelboards or assemblies are marked “Class CTL” or “CTL.” A Class CTL breaker, because of its size or configuration in conjunction with the physical means provided in Class CTL panelboards, prevents more circuit breaker poles from being installed than the number for which the assembly is designed and rated. A Class CTL panelboard is a circuit limited panelboard. Both “half-sized” and “full-sized” breakers may be marked “Class CTL.” When properly installed, Class CTL circuit breakers will comply with the Lighting and Appliance Branch-Circuit Panelboard requirements in previous editions of the National Electrical Code.
32. “Delta” – A delta breaker is a 3-pole — 3-phase circuit breaker intended to have two poles connected to a bus structure and a third pole isolated, and is marked “For Replacement Use Only.”
33. 2-Pole — 3-Phase Rated – A 2-pole circuit breaker marked “1-Phase — 3-Phase” or “1Ø — 3Ø” may be used on 3-phase, corner-grounded delta circuits, or on single-phase circuits.
34. 3-Pole — 1-Phase Rated – 3–pole circuit breakers are suitable for use on 3-phase systems only, unless marked to indicate use on 1-phase systems, such as, “Also Suitable for Use in Single Phase Applications up to ___V,” or an equivalent statement. The specified voltage is the maximum voltage the 3-pole circuit breaker may be applied in a single-phase system. A 3-pole breaker may be used in place of a 2-pole breaker on a 3-phase system, such as a 2-pole breaker used in a branch circuit that is actually two legs of a 3-phase system, and will be marked “Use outside poles for single phase applications” or “Use any two poles for single phase applications” or an equivalent statement.
35. 4-Pole — 3-Phase Rated – 4-pole circuit breakers are suitable for use on 3-phase systems where a switched neutral is required. The fourth pole is provided either without overcurrent protection or with overcurrent protection of 50 or 100 percent of the other poles. The fourth (neutral) pole of a 4-pole circuit breaker is marked “Protection – _% In”. The percentage indicated is 0, 50 or 100.
36. Multi-Wire Circuit – A multi-pole circuit breaker intended for use in a multi-wire circuit only is marked with a combination voltage rating only, such as 480Y/277 V ac, provided a 3-pole breaker intended only for use in a single-phase multi-wire circuit includes in its marked voltage rating the term “Only for Use in 1-phase Circuits” or an equivalent. The neutral pole of a 3-pole breaker marked only for use in single phase circuits will be clearly identified.
37. DC Rated – A 3-pole circuit breaker rated 250 V dc or less is acceptable for use in DC voltage systems, when marked to indicate its DC voltage rating and it is necessary to use two of the poles to control the circuit. Circuit breakers rated more than 250 V dc are generally intended to be connected with poles in series and are marked with a wiring diagram indicating how poles should be wired in series. If the circuit breaker is suitable for multiple wiring configurations, the circuit breaker is provided with a separate document that details the markings, and a reference to the document on the circuit breaker.
38. 100 Percent Continuous Rated – Unless otherwise marked for continuous use at 100 percent of its current rating, a circuit breaker is intended for use at no more than 80 percent of its rated current where in normal operation the load will continue for three hours or more. A breaker with a frame size of 250 A or more, or a multi-pole breaker of any current rating greater than 250 V, may be marked to indicate it is suitable for continuous use at 100 percent of its current rating. The marking is “Suitable for continuous operation at 100 percent of rating only if used in a circuit breaker enclosure Type ____or in a cubicle space______by_____ by _____ inches” or an equivalent statement. This type of breaker may also be marked to indicate it is to be used with wire sized for a 75°C conductor with 90°C insulation and used with 90°C wire connectors.
39. “SWD” – A circuit breaker rated 15 or 20 A, 347 V ac or less, may be marked “SWD” and is suitable for switching fluorescent lighting loads on a regular basis.
40. Independent Trip – A 2-pole circuit breaker that does not have an internal common trip feature is marked “Independent Trip” or “No Common Trip.” An external handle tie alone does not qualify as a common trip mechanism — a breaker of this type is marked to indicate it is an independent trip breaker.
41. Special Characteristics – If the proper operation of a circuit breaker depends on a special characteristic, such as polarity or position, the breaker is marked to indicate this characteristic. If this includes a barrier, shield or similar member, the breaker is marked with all the necessary information. If it is necessary to replace a part, such as a barrier or shield, the marking also includes replacement instructions.
42. For Replacement Not CTL – The marking “For replacement use only not CTL assemblies” appears on breakers that do not have means to prevent their installation in Class CTL assemblies. These breakers are intended for replacement in older assemblies still in service, which pre-dates the Class CTL requirements for circuit breakers and panelboards.
43. Special Purpose Not General – Circuit breakers marked “Special purpose not for general use” have special features limiting their suitability to specific applications. Instructions are provided by the manufacturer detailing these applications.
44. “HID” – A circuit breaker rated 50 A maximum, 480 V or less, and intended to switch high intensity discharge (HID) lighting loads on a regular basis is marked “HID.”
45. Remotely Operated Circuit Breaker – A circuit breaker that can be opened remotely, such as by a utility, for purposes of shedding loads. These circuit breakers are marked “Remotely Operated” and are provided with a separate label marked: “Remotely-operated circuit breaker installed in this equipment” with instructions for attaching the label to the equipment.