Authors: Kerry Bell, Principal Engineer, William Henry Merrill Society

Carlos Pacheco, Senior Product Manager

Replacing each sprinkler located within a facility can be costly, labor-intensive and disruptive.  

NFPA 25 offers another option for certain sprinklers that have reached a milestone in their service life: representative sample testing. Instead of moving straight to mass replacement at age-based intervals, facility owners can use laboratory testing to determine whether sprinklers represented by the sample may remain in service.  

This creates a more informed path forward — one that can support compliance while helping limit unnecessary replacement-related cost and operational disruption. Except for sprinklers using a dynamic O-ring water seal, the overall results of UL Solutions testing of sprinklers sampled for installation sites indicate a very high percentage of normal operation based on the criteria referenced in NFPA 25.

For facility owners and managers, that can mean:

  • A more targeted approach to replacement spending
  • Less downtime and disruption tied to large-scale sprinkler replacement
  • Documented test results to support maintenance decisions
  • A standards-based path for continued service when results support it

What NFPA 25 allows

NFPA 25 provides minimum inspection, testing and maintenance requirements for water-based fire protection systems, including an option to use representative sample testing for certain sprinklers at specified intervals. 

Representative sample testing

Under NFPA 25 (2026 edition), Section 5.3.1, sprinklers that have reached applicable testing or replacement intervals may remain in service if a representative sample is laboratory tested and shown to perform as intended. 

Per Section 5.3.1.2, a representative sample must include: 

  • A minimum of four sprinklers or 1% of the sprinklers in the sample area, whichever is greater 
  • Sprinklers representing each manufacturer and sprinkler type within the sampled area 
  • Exclusion of previously replaced sprinklers from the sample 

When the representative sample meets the applicable test requirements, the remaining sprinklers represented by that sample may continue in service under the standard. 

Built‑in safeguards

NFPA 25 also sets a clear threshold for action: Section 5.3.1.3 requires that if any sprinkler in the sample fails to meet the test requirements, all sprinklers represented by that sample must be replaced. 

That gives facility teams a defined, documented basis for deciding when continued service is appropriate and when replacement is required. 

Representative sample testing does not replace NFPA 25 requirements to replace sprinklers with conditions such as leakage, field painting, physical damage, loss of glass bulb fluid, or corrosion or loading considered detrimental to sprinkler performance. 

A practical path for large portfolios

This option can be especially relevant for commercial properties, healthcare facilities, senior living communities, campuses and other organizations managing large or multibuilding portfolios where large-scale sprinkler replacement can strain budgets and operations. 

For organizations focused on protecting people and property while managing maintenance decisions carefully, representative sample testing offers a practical, standards-based option under NFPA 25. 

UL Solutions tests sprinklers sampled from field installations as a service to inspection authorities, the sprinkler industry, the insurance industry and property owners. Visit our Field Sprinkler Testing Tool page to learn more.